Instruction Manual alpha-pH 1000
21
1) Follow directions in 7.3.1 to enter Control Relay mode.
2) Press the ENTER key. Scroll with the or key until the upper
display shows the hysteresis (dead band) value and the lower display
shows “HYS”.
3) Press the or keys to enter your hysteresis value for Set point 1
(Set point 2). Your controller will activate at the value you select.
4) Press the ENTER key to confirm your selection.
5) Proceed to 7.3.5 step 3, or return to Measurement mode by pressing the and keys simultaneously
(escape).
NOTE: Please refer to Appendix 3 for a graphical representation of the Hysteresis.
7.3.5 Setting an on-delay time lag
You can set as time delay for each relay, which stops the relay from switching on the moment the set point is
exceeded. This controller lets you set a 0 to 2000 second time delay before the relay activates.
1) Follow directions in 7.3.1 to enter Control Relay mode.
2) Press the ENTER key. Scroll with the or key until the upper
display shows “on delay” time and the lower display shows “On.d”.
3) Press the or key to enter on-delay time for Set point 1 (Set point
2). The controller will delay activation for the number of seconds (0 to
2000) you select.
4) Press the ENTER key to confirm your selection.
5) Proceed to 7.3.6 step 3, or return to Measurement mode by pressing the and keys simultaneously
(escape).
7.3.6 Setting an off-delay time lag
You can set as time delay for each relay, which stops the relay from switching off the moment the value
reached the set point and hysteresis. This controller lets you set a 0 to 2000 second time delay before your
relay deactivates.
1) Follow directions in 7.3.1 to enter Control Relay mode.
2) Press the ENTER key. Scroll with the or key until the upper
display shows “off delay” time and the lower display shows “OF.d”.
3) Press the or key to enter on-delay time for Set point 1 (Set point
2). Your controller will delay activation for the number of seconds (0 to
2000) you select.
4) Press the ENTER key to confirm your selection.
5) Continue with Advanced Set-up mode procedures, or return to Measurement mode by pressing the
and keys simultaneously (escape).
0.50
pH
HYS
SETUP
HOLD
0
On.d
SETUP
HOLD
0
OF.d
SETUP
HOLD