Appendix 1: Simple Explanation on the Function of Hysteresis
The controller relay activates when the set-
point is reached. In the reverse direction, it
does not de-activate when the value
reaches the set-point. Instead, it continues
to be active till the value reaches the
amount set by the Hysteresis band.
Appendix 2: Factory Defaults
Resetting the controller to factory default settings (See program P7.0) clears
all calibration data and most other setup functions.
The following settings will remain unchanged:
1. Measurement range
2. Temperature compensation mode (ATC or MTC)
3. Temperature offset calibration value, if in ATC mode.
Conductivity Defaults
Conductivity range Remains unchanged at last selected range
Set point 1 10% full scale / Hyst. 5% full scale / Low
Set point 2 90% full scale / Hyst. 5% full scale / High
Temperature Defaults
Temp. Compensation mode remains unchanged
MTC mode reset to 25
o
C if in MTC mode
ATC mode remains at last calibration if in ATC mode
Temperature Coefficient 2.1 %
Normalization Temperature 25.0
o
C
200 300 1700 1800
RELAY OFF
HYSTERESIS BAND
FORWARD DIRECTION
REVERSE DIRECTION
SP1
SP2
RELAY ON
SP1 Set to LO
SP2 Set to HI